Date: August 2002
Ref: ACIG 2002-08-003
Dear Rockwell Automation Customer,
The purpose of this Product Service Advisory is to inform you of a functional issue that exists with:
2711-x10x9 PanelView 1000 Color Series D Revision A and Gray Scale Series B Revision A, Communication option "9" DH485 (RS232)
This Advisory explains the functional issue and the steps being taken to rectify the situation.
With the 2711 PanelView 1000 Color Series D Revision A and Gray Scale Series B Revision A, the following functional issue exists:
Functional Issue - Communications to the Logic Controller on DH485 (RS232) will be either intermittent or non-existent depending on the grounding connection on the communications port.
In the PanelView 1000 Color Series D Revision A and the PanelView 1000 Gray Scale Series B Revision A, a re-designed motherboard was introduced by Rockwell Automation. The design of the motherboard inadvertently omitted proper ground on pin 5 of the RS232 port, causing the communications problems.
- Product Identification -
Identification information is on the Product Identification label located on the back of the product.
The functional issue described above has been corrected in the following versions of
the PanelView 1000:
-Requested Customer Action-
Each notified customer should take the following actions:
We require and appreciate your immediate cooperation in this matter. If you have any questions, please contact us.
Clark Kromenaker David Kaley
Product Manager Sr. Marketing Engineer
PanelView Standard Products PanelView Standard Products
Rockwell Automation Rockwell Automation
Tel: 414-382-3451 Tel: 414-382-3451
ckromenaker@ra.rockwell.com dckaley@ra.rockwell.com